The load on a hydel plant varies from a minimum of 10,000 kW to a maximum of 35,000 kW. Two turbo-generators of capacities 20,000 kW each have been installed. Calculate Plant factor.

(a) 50%

(b) 51%

(c) 56.2%

(d) 59.7%

I had been asked this question in an interview for job.

This intriguing question originated from Hydropower in section Hydro Electric Power of Irrigation Engineering

1 Answer

0 votes
by (106k points)
The correct choice is (c) 56.2%

Explanation: Plant factor can be defined as the ratio of the energy actually produced (Average load) to the maximum energy that can be produced at a particular time.

Since two turbo generators are installed, the total installed capacity = 40000 kW

P.F = [(10000 + 35000) / 2] / 40000 = 56%.

Related questions

We welcome you to Carrieradda QnA with open heart. Our small community of enthusiastic learners are very helpful and supportive. Here on this platform you can ask questions and receive answers from other members of the community. We also monitor posted questions and answers periodically to maintain the quality and integrity of the platform. Hope you will join our beautiful community
...